Alarms and alerts
7EN05-0336-03
7. Click Start to begin sag/swell limit learning.
When setpoint learning is in progress, an asterisk is displayed next to the
setpoint.
Click Abort to stop sag/swell limit learning.
8. Apply the learned sag/swell limits.
– Automatic: the limits are automatically applied unless there are issues with the
learning process.
– Manual: navigate to Alarming > Sag/Swell. Select Voltage and click Learn.
Click Install to apply the learned limits.
NOTE: If you click Install while learning is in progress (in either manual or
automatic installation mode), it stops the learning process and prompts you for
confirmation that you want to stop learning and install the learned limits. Once
you have confirmed, the learned limits are automatically installed or prepared
for manual installation.
Sag/swell limit learning parameters
Parameter
Value/Range
Install mode
Automatic,
Manual
Duration
1-365
Description
Automatic: the learned values are automatically
applied.
Manual: the learned values are stored for you to
review and enter.
Days for maximum learning duration.
9410 series
163