Viewing Files Using Your Meter's Webpages; Creating Custom Webpages For Your Meter - Siemens 9410 Series User Manual

Hide thumbs Also See for 9410 Series:
Table of Contents

Advertisement

9410 series

Viewing files using your meter's webpages

Example

Creating custom webpages for your meter

110
6. Select Setup to view and edit your meter's configuration.
You can load files of a variety of standard formats, such as *.pdf, *.jpg and *.png into
the webpage folders on your meter's internal FTP site where they can be viewed using
your meter's webpages.
Videos in *.mp4 format can be played in most browsers. The filenames must be
compatible with your meter's FTP filename requirements.
NOTE: Image files are shown at full-size (100%). Scale images to the desired size
before loading them onto your meter's internal FTP site.
1. Access your meter's internal FTP site.
2. Open the web folder. Copy your file into the subfolder that corresponds to the
webpage main menu tab you want to access your file from.
3. Connect to your meter's webpages. Select the main menu item that corresponds
to the folder where you stored your file in step 2. Your file is listed in the webpage
menu.
4. Select your file from the webpage menu to view.
To view a schematic diagram (oneline.pdf) of your power system from the Monitoring
menu of your meter's webpages:
1. Access your meter's internal FTP site.
2. Copy oneline.pdf into web > monitoring.
3. Access your meter's internal webpages and select the Monitoring menu.
4. In the webpage menu click oneline.pdf to view your power system schematic.
Related Topics
FTP
FTP filename requirements
You can create custom webpages to view data or access configuration parameters
from your meter.
Download the your meter's Modbus registers map from www.usa.siemens.com/pds.
1. Connect to your meter's internal FTP site.
2. Go to web > examples. Select samplereadings.html to create a data value
webpage, or select sampleconfiguration.html to create a configuration parameters
webpage.
3. Save a copy of the sample file. This filename is the webpage name.
4. Open your webpage in an HTML or webpage editor program.
5. Modify the webpage to reference the desired meter data or parameters from the
Modbus registers map, and update the other fields where required.
Meter webpages
7EN05-0336-03