Communications
Parameter
Enable SNMP .
SNMP Port Number
System contact
System name
System location
Read-only Community Name
Read-write Community Name
Enable SNMP Traps
Enable High Priority Alarms
Enable Med Priority Alarms
Enable Low Priority Alarms
Report Buffer Size
Report Hold Time
Trap Rcvr1 Addr -
Trap Rcvr4 Addr
SNMP implementation
MIB files
Community strings
7EN05-0336-03
3. Configure your meter's SNMP parameters by selecting the parameter value.
Range
Description
Yes/no
Enables or disables SNMP on your meter.
161 (default)
Enter your meter's SNMP port number.
Enter the name of your SNMP system administrator.
Enter a descriptive name for your meter.
Enter your meter's location.
Enter the community string used for SNMP get (read-only) requests.
Enter the community string used for SNMP set (read/write) requests. NOTE:
You can use the read/write community string for SNMP get (read-only)
requests.
Enable/disable
Enables or disables SNMP trapping on your meter.
Yes/no
Enables trapping of events that create high priority alarms.
Yes/no
Enables trapping of events that create medium priority alarms.
Yes/no
Enables trapping of events that create low priority alarms.
1 - 30
Enter the maximum number of trap messages to be stored before the trap
messages are sent. Traps are sent when the number of trap messages is
equal to or greater than this value.
1 - 300 seconds
Enter the maximum duration for trap messages to be held. Trap messages
are sent when the time after a trap event has occurred is equal to or greater
than this value.
Enter up to four trap receiver IP addresses, where trap messages will be
sent.
4. Click Apply to configure the meter's SNMP parameters.
Your meter is compliant with MIB-II as defined by the standard MIB file RFC 1213.
SNMP requires that you load your meter's ION MIB file (available for download from
www.usa.siemens.com/pds) into the NMS.
You must install RFC 1213, which is required to read basic network information for the
meter (for example, TCP/IP traffic or number of packets received), if it is not included
with your SNMP manager software.
A community string is a text string which acts to help authenticate requests from the
NMS to your meter.
There are two community strings on your meter:
Read Only Community: this community string is used by SNMP get (read-only)
requests. The read only community string's initial factory-set value is public.
Read Write Community: this community string is used by SNMP set (read/write)
requests. The read write community string's initial factory-set value is private.
NOTE: You can also use the read write community string for SNMP get (read-only)
requests.
9410 series
87