Siemens 9410 Series User Manual page 68

Hide thumbs Also See for 9410 Series:
Table of Contents

Advertisement

9410 series
68
3. Select Communications > Serial Settings .
4. Select a setting and then click Edit to configure the setting to match your
communications system.
Serial communications settings available using ION Setup
Parameter
Values
Protocol
ION, Modbus RTU, Modbus
Master, DNP v3.00,
EtherGate, GPS: Truetime/
Datum, GPS: Arbiter, GPS:
Arbiter-Vorne, Factory,
None
Baud Rate
2400, 4800, 9600, 19200,
38400, 57600, 115200
Rx Timeout
0.1–15
Unit ID
1 to 9999
Serial Port
8N1, 8N2, 8E1, 8E2, 8O1,
8O2
RS485 Bias
Off, On
1
Only applies to a subset of protocols
Configuring serial communications settings using the webpages
You can use the meter's webpages to configure your serial communications settings.
Before configuring serial parameters, make sure you have a unique unit ID for your
meter and know the serial network settings (protocol, baud rate, parity and stop bits).
1. Connect to your meter's webpages using the meter's IPv4 address or its IPv6 link
local address, or use self-discovery then double-clicking the meter's network icon.
2. Navigate to Setup > Serial Port.
3. Enter the appropriate value for the settings.
Communications
Description
Sets the communications protocol for your
meter's RS-485 port
NOTE: the
setting stops
NONE
communications using this port.
Sets the data rate, in bits per second
Sets the transmit delay (timeout for receiving an
entire message from a device) in seconds
Sets the meter's unique ID on the RS-485
network
NOTE: Modbus serial device range 1 to
247
Sets the parity and stop bits for the port
Turns on biasing when mastering devices over
the RS-485 port
1
7EN05-0336-03