Enclosure Ventilation Grills

Use grills to ventilate the enclosure. The grills must provide 24 square inches of free area opening (12 square
inches each) into the enclosure cavity. The grills must be located within 24" of the appliance.
The grills must be attached directly to the
chase or enclosure cavity.
The grills must have 1/4" screen to prevent
debris, etc. from entering the enclosure.
The grills should not be placed in a location
where they could become blocked.
The ventilation air for the enclosure MUST be
drawn from outdoor air only.
Facing may be applied over the flange of the
grills but cannot protrude over the screened
opening.
The grills may be painted.
The grills must be located within 24" of the
appliance.
 
The grills must be located within the bottom 6"
of the chase.
Example: If (w) = 4" and (h) = 2"
4" x 2" = 8 square inches
8"
< 12" (the minimum)
NOT LARGE ENOUGH
Example: If (w) = 12" and (h) = 2"
6" x 2" = 12 square inches
12"
> 12" (the minimum)
LARGE ENOUGH
 
 
© Travis Industries, Inc.
(qualified installers only)
 
3/20/23 - 1580
 
 