Strain relief

17.2 Installing

17.2
Installing
Requirement
• The Industrial Ethernet/PROFINET cables are not inserted on the BusAdapter. The inserted
Industrial Ethernet/PROFINET cables hamper the mounting of the strain relief.
• BusAdapter and strain relief can be mounted separately.
Tools required
Screwdriver TX10 (torx).
Procedure
To install the strain relief, follow these steps:
1. Press the strain relief below the BusAdapter seat of the PROFINET device.
Figure 17-2  Strain relief before mounting
2. Fasten the strain relief (1 screw with 0.7 to 0.8 Nm tightening torque).
3. Plug the BusAdapter into the PROFINET device.
4. Screw the BusAdapter to the PROFINET device (1 screw with 0.25 Nm tightening torque).
92
Equipment Manual, 10/2022, A5E41449003-AC
BusAdapter