BusAdapter BA SCRJ/RJ45

10.4 Technical specifications

LED
LK1/LK2
Not relevant
10.4
Technical specifications
Technical specifications of BusAdapter BA SCRJ/RJ45
The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AP20-0AA0/td?dl=de).
Article number
Supports protocol for PROFINET IO
Cable length
Ambient temperature during operation
Altitude during operation relating to sea level
58
MT
Fiber-optic error
on
Maintenance demanded: attenu­
ation through the fiber-optic cable
is already so high that operation
will soon no longer be possible.
General information
Product type designation
HW functional status
Interfaces
Number of PROFINET interfaces
Number of RJ45 ports
Number of SCRJ ports
Number of LC ports
PCF
Plastic FOC (POF)
PCF-GI
Cu conductors
Ambient conditions
horizontal installation, min.
horizontal installation, max.
vertical installation, min.
vertical installation, max.
Meaning
Causes and measures for the transmission
route:
6ES7193-6AP20-0AA0
BA SCRJ/RJ45
from FS04
1; 2 ports (SCRJ + RJ45)
1
1
0
100 m
50 m
250 m
100 m
-25 °C
60 °C
-25 °C
50 °C
Remedy
Replace the fiber-optic cable if damaged or
aged.
Ensure correct installation of the PROFINET
plugs or PROFINET connectors.
Adhere to maximum length of 50 m for
POF cable or 100 m for PCF cable.
Ensure that the FOC connectors fit
securely.
Equipment Manual, 10/2022, A5E41449003-AC