LED
LK1/LK2
MT1/MT2
Not relevant
7.4

Technical specifications

Technical specifications of BusAdapter BA 2×SCRJ
The following table shows the technical specifications as of the issue date. You can find a
data sheet including daily updated technical specifications on the Internet
(https://support.industry.siemens.com/cs/de/en/pv/6ES7193-6AP00-0AA0/td?dl=de).
Article number
Supports protocol for PROFINET IO
Cable length
Ambient temperature during operation
Altitude during operation relating to sea level
BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC
Fiber-optic error
on
Maintenance demanded: attenu­
ation through the fiber-optic cable
is already so high that operation
will soon no longer be possible.
General information
Product type designation
HW functional status
Interfaces
Number of PROFINET interfaces
Number of SCRJ ports
Number of LC ports
PCF
Plastic FOC (POF)
PCF-GI
Ambient conditions
horizontal installation, min.
horizontal installation, max.
vertical installation, min.
vertical installation, max.
Installation altitude above sea level, max.
Meaning
Causes and measures for the transmission
route:
6ES7193-6AP00-0AA0
BA 2xSCRJ
from FS04
1; 2 ports (switch) SCRJ FO
2
0
100 m
50 m
250 m
-25 °C
60 °C
-25 °C
50 °C
5 000 m; restrictions for installation altitudes >
2 000 m, see ET 200SP system manual
BusAdapter BA 2xSCRJ
7.4 Technical specifications
Remedy
Replace the fiber-optic cable if damaged or
aged.
Ensure correct installation of the PROFINET
plugs or PROFINET connectors.
Adhere to maximum length of 50 m for
POF cable or 100 m for PCF cable.
Ensure that the FOC connectors fit
securely.