Pin assignment
The following table shows the signal name and description of the pin assignment of the
BusAdapter BA 2×LC:
Table 8-1  Industrial Ethernet/PROFINET pin assignment with BusAdapter BA 2xLC
Requirements
• Prepare the IE FC FO cable with the IE FC FO LC plug connectors. For detailed instructions,
refer to the assembly instructions Preparing IE FC FO Cable with the plug-in connector IE
FC FO LC Plug (A5E36312721).
• When installing the fiber-optic cable, make sure the bending radius is not less than
permitted:
– IE FC FO Standard Cable GP (62.5/200/230): 70 mm
– IE FC FO Trailing Cable (62.5/200/230) (6XV1847-2C): 88 mm
• The maximum lengths of the fiber-optic cables are as follows:
– IE FC FO Standard Cable GP (62.5/200/230): 2 km
– IE FC FO Trailing Cable (62.5/200/230): 2 km
• When the interface module is the last device of the fiber-optic cable network, the
unoccupied fiber-optic cable interface must be closed with a blanking plug. When the
modules ship, the blanking plugs are inserted in the PROFINET sockets of the BusAdapter.
Procedure
To connect PROFINET IO to the PROFINET device via the BusAdapter BA 2xLC, follow these
steps:
1. Plug the BusAdapter BA 2xLC into the PROFINET device.
2. Screw the BusAdapter BA 2xLC to the PROFINET device (1 screw with 0.25 Nm tightening
torque). To do this, use a screwdriver with a 3 to 3.5 mm blade, alternatively TX10.
3. Remove the blanking plugs from the PROFINET sockets.
BusAdapter
Equipment Manual, 10/2022, A5E41449003-AC
View
Signal name
Receive Data
Transmit Data
BusAdapter BA 2xLC
8.2 Connecting
Description
43