YASKAWA 1000 Series Installation Manual page 23

Ac drive option, motor encoder feedback, heidenhain ern1387 interface
Hide thumbs Also See for 1000 Series:

Advertisement

8.
Set drive parameters in
The leading pulse determines the motor rotation direction. A PG encoder signal with
leading A phase is considered to be rotating forward (counter-clockwise when
viewing rotation from motor load side).
Figure 10
After connecting the PG encoder outputs to the option, apply power to the drive and
manually rotate the motor and check the rotation direction by viewing monitor U1-05
on the digital operator.
WARNING! Ensure the drive RUN circuit is locked out and a RUN command is not possible before
attempting to manually rotate the motor shaft with the drive powered on. Failure to comply may cause injury
to personnel due to inadvertant equipment movement.
Reverse motor rotation is indicated by a negative value for U1-05; forward motor
rotation is indicated by a positive value.
If monitor U1-05 indicates that the forward direction is opposite of what is intended,
set drive parameter F1-05 to 1 to switch the direction of how the option reads pulses
from the PG encoder output.
Note: If the drive is initialized using A1-03 =1110, 2220, or 3330, the value for F1-05 will reset to
factory default and the parameter will need to be adjusted again to switch the direction.
YASKAWA ELECTRIC TOBP C730600 52D 1000-Series Option PG-E3 Installation Manual
Table 6
for proper motor rotation.
A
Phase
E3
B
Phase
Figure 11 Displacement of A and B Phases
5 Installation Procedure
The A phase leads, followed
by the B phase displaced at 90 degrees
Time →
23