Table of Contents

Advertisement

5.2.9

$AA1

Description
Performs an Analog Input Zero Calibration on the Module.
Syntax
$AA1[CHKSUM](CR)
$
Delimiter character
AA
The address of the module to be calibrated in hexadecimal
format(01 to FF)
1
Command for zero calibration.
Response
Valid Command
Invalid Command
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate an invalid command.
AA
The address of the responding module in hexadecimal format (01 to FF)
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Examples
Command
$1B1
Response
!1B
Performs zero calibraction of all channels in address 27, and returns a
response indicating that the command was successful.
Examples
Command
$1C1
Response
?1C
Performs zero calibraction of all channels in address 28, and returns a
response indicating that the command was not successful. Because the
module don't perform "Enabled/Disabled calibraction" command.
※Related Commands: $AA0、~AAEV
ICP DAS, ZT-2005-C8 User Manual, Version v1.0.1
Copyright © 2014 by ICP DAS Co., Ltd. All Rights Reserved.
!AA[CHECKSUM](CR)
?AA[CHECKSUM](CR)
Page 27