Table of Contents

Advertisement

5.2.3

%AANNTTCCFF

Desctiption
This command is used to set the configuration of a specific module.
Syntax
%AANNTTCCFF[CHKSUM](CR)
%
Delimiter character
AA
The address of the module to be configured in hexadecimal format
(01 to FF)
NN
The new address of the module in hexadecimal format (01 to FF)
TT
00 (Reserved)
CC
0A (Reserved)
FF
The command used to set the data format and checksum. See
Section 4.2 for details of the data format.
00:Disabled checksum, and use Engineering units.
40:Enabled checksum, and use Engineering units.
02:Disabled checksum, and use 2's Complement Hexadecimal.
42:Enabled checksum, and use 2's Complement Hexadecimal.
Response
Valid Command
Invalid Command
!
Delimiter character to indicate a valid command
?
Delimiter character to indicate a invalid command
AA
The address of the responding module in hexadecimal format (01 to
FF)
NN
New address of the module in hexadecimal format (01 to FF)
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Examples
Command %0101000A00
Response
!01
Setting the address 01 to 01, disable checksum and use engineering units.
Examples
Command %1B01000A42
Response
!01
Setting the address 27 to 01, enable checksum and use 2's Complement
Hexadecimal.
※Effect after reboot, and Related Commands: $AA2
ICP DAS, ZT-2005-C8 User Manual, Version v1.0.1
Copyright © 2014 by ICP DAS Co., Ltd. All Rights Reserved.
!NN[CHECKSUM](CR)
?AA[CHECKSUM](CR)
Page 21