Table of Contents

Advertisement

5.2.21

@AAA2CiToo

Desctiption
This command is used to set the offset of temperature for a specific Analog Input
channel.
Syntax
@AAA2CiToo[CHKSUM](CR)
@
Delimiter character.
AA
The address of the module to be read in hexadecimal format (01 to
FF).
A2
Command to set the offset of temperature for a specific Analog Input
channel.
Ci
The number of channels. (The first channel is channel 0)
Too
The offset value of ℃ or ℉. The range of oo is -12.8℃ to 12.7℃, or
-12.8℉ to 12.7℉.
For example, oo equal to 01 is mean that +0.1℃, oo equal to 02 is mean
that +0.2℃, oo equal to FF is mean that -0.1℃, oo equal to FE is mean
that -0.2℃.
Response
Valid Command
Invalid Command
!
Delimiter character to indicate a valid command.
?
Delimiter character to indicate an invalid command.
AA
The address of the responding module in hexadecimal format (01 to
FF)
There will be no response if the command syntax is incorrect, there is a
communication error, or there is no module with the specified address.
Examples
Command
@1BA2C0T0A
Response
!1B
Sets the offset value +1.0℃ of channel 0 in module address 27, and returns a
valid response.
Examples
Command
@1BA2C5TF0
Response
!1B
Sets the offset value -1.6℃ of channel 5 in module address 27, and returns a valid
response.
※Related Commands:@AAA3Ci
ICP DAS, ZT-2005-C8 User Manual, Version v1.0.1
Copyright © 2014 by ICP DAS Co., Ltd. All Rights Reserved.
!AA[CHKSUM](CR)