15. Click OK twice and download the program to the PLC.
The connection looks like the one in

6.1.3 EtherNet/IP Configuration Using Generic Ethernet Module

To create an implicit Class 1 configuration to the ZMX using EtherNet/IP when using a ControlLogix family PLC, configure the
ZMX as a "Generic Ethernet Module". The following is a sample setup of a Banner device using RSLogix5000
5000 Logix Designer software:
1. Add a generic Ethernet module to the PLC's Ethernet card.
a) Right-click and select New Module.
Figure 35. Module Definition—Data Type
Figure 36. Download to the PLC
Figure 36
on page 31.
www.bannerengineering.com - Tel: + 1 888 373 6767
ZMX Series 3D Time of Flight Sensor
®
or Studio
31