Performing a keyboard test
Perform a keyboard test to confirm that the buttons are working correctly.
To perform a keyboard test:
1. Select Tests from the Main menu.
2. Select UI tests, and then Keyboard test.
3. Press a button on the control panel interface.
A message appears on the LCD to confirm that the button has been pressed.
4. Repeat step 3 for all buttons.
5. Press F2 (Exit).
Performing an LCD test
Perform an LCD test to confirm that the LCD is working correctly.
To perform an LCD test:
1. Select Tests from the Main menu.
2. Select UI tests, and then LCD test.
A test pattern displays on the LCD to help identify the location of defective
pixels.
3. Press F2 (Exit).
Viewing the alarm counter
Select the Alarm counter option to view the total number of fire alarms recorded
by the control panel. The alarm counter value cannot be reset.