Ziton ZP2-AF1-S Operation Manual page 24

Hide thumbs Also See for ZP2-AF1-S:
Table of Contents

Advertisement

Test
Tests are indicated as follows:
The General Test LED is steady
If a zone board is installed, the corresponding zone Disabled/Test LED is
steady (if the corresponding zone is included on the zone board)
The control panel buzzer sounds intermittently (short tone)
For more information on the test, press F1 (Show Events) and then select
Conditions.
Low battery
WARNING:
This is a critical indication and your property may not be fully
protected. If your control panel indicates low battery, contact your installation or
maintenance contractor immediately and ask them to restore power or, if this is
not possible, to replace the batteries.
Low battery indicates that the control panel is running on battery power and that
the remaining charge may be insufficient for continued operation.
Low battery is indicated as follows:
The General Fault LED is flashing
The Low battery LED is steady
An initial warning message indicating the low battery status is displayed on
the LCD
If the power issue is not fixed, the batteries will continue to discharge until a
second warning message is displayed indicating that the control panel will
shut down
The buzzer sounds intermittently (long tone)
When the batteries are completely discharged, the control panel shuts down to
protect the batteries and there are no further indications.
If power is re-established before the control panel shuts down, the control panel
returns to its former status. If not, the control panel date and time must be
reconfigured once power is restored.
Notes
Customers who wish to obtain maximum standby time from batteries (24 to
72 hours) may see this fault indication.
A low battery indication means that the batteries are discharged and does not
indicate that they are defective.
18
ZP2-A Series Operation Manual

Advertisement

Table of Contents
loading

Table of Contents