Public Level Operation - Ziton ZP2-AF1-S Operation Manual

Hide thumbs Also See for ZP2-AF1-S:
Table of Contents

Advertisement

Public level operation

Public level operations are those that can be performed by any user. No
password is required to perform tasks at this level.
This user level lets you:
Silence the buzzer
Cancel an active sounder, fire routing, or fire protection delay
Manually start evacuation sounders
View current events
View support information
Silencing the buzzer
To silence the control panel buzzer, press the Panel Silence button. A steady
Panel Silence LED indicates that the buzzer was silenced.
Note:
Depending on the control panel configuration, the buzzer may re-sound for
each new event reported.
Cancelling an active sounder delay
If a sounder delay is enabled and active (counting down), press the Sounder
Delay button to cancel the delay and activate sounders immediately.
A sounder delay is indicated as follows:
A steady Sounder Delay LED indicates that a delay is enabled
A flashing Sounder Delay LED during a fire alarm indicates that the
configured delay is active (sounders are activated when the configured delay
elapses or when the delay is cancelled)
A fire alarm activated by a manual call point overrides any configured delay and
activates the sounders immediately.
22
ZP2-A Series Operation Manual