Environment Correction - Energizer EZG2001i Original Instructions Manual

Hide thumbs Also See for EZG2001i:
Table of Contents

Advertisement

14. ENVIRONMENT CORRECTION

The rated power output is based on the standard condition as follows:
Ambient temperature: 25℃
Relative humidity: 30%
Factor of environment correction C:
Altitude(m)
0
500
1000
2000
3000
4000
NOTE:
Relative humidity 60% correction factor C-0.01;
Relative humidity 80% correction factor C-0.02;
Relative humidity 90% correction factor C-0.03;
Relative humidity 100% correction factor C-0.04;
25
30
1
0.98
0.93
0.91
0.87
0.85
0.75
0.73
0.64
0.62
0.52
0.52
Ambient temperature℃
35
0.96
0.89
0.82
0.71
0.60
0.50
- 91 -
ORIGINAL INSTRUCTIONS
40
45
0.93
0.90
0.87
0.84
0.80
0.78
0.69
0.66
0.58
0.56
0.48
0.46

Advertisement

Table of Contents
loading

Table of Contents