4 PROCEDURES AND SETTINGS BEFORE OPERATION

4.6 Checking the module's state (Hardware test)

Confirm that the R2 operates normally as a single module. Always carry out this test
before structuring the system.
Execute the test with the following procedure.
Disconnect the CC-Link dedicated cable for
the data link from R2.
Mount an RS-232-C single module loopback connector.
Set the data link related hardware.
·
Set the data link transmission speed setting switch.
Set the mode setting switch to "D".
(hardware test mode)
Turn ON the R2 power.
Confirm the RS-232-C ERR. LED
*1
The specifications of the RS-232-C single module loopback connector are shown
below.
Create the RS-232-C single module loopback connector shown below.
R2 side (DTE)
Signal abbrev.
CD
RD (RXD)
SD (TXD)
DTR (ER)
SG
DSR (DR)
RS (RTS)
CS (CTS)
IMPORTANT
During the hardware test mode, the check data is transmitted to the data link when
checking the data link loopback, so always disconnect the data link wiring.
Start
*
2
*
Single module loopback
Pin No.
connector
1
2
3
4
5
6
7
8
9
4 - 11