Check Of Module Condition (Self-Loopback Test) - Mitsubishi MELSEC-Q Series User Manual

Hide thumbs Also See for MELSEC-Q Series:
Table of Contents

Advertisement

6 TROUBLESHOOTING

6.7 Check of Module Condition (Self-loopback Test)

*1: Only for the Q02/Q02H/Q06H/Q12H/Q25H/Q02PH/Q06PH/Q12PH/Q25PHCPU and C Controller module.
RUN
When normal
ON
ON
When faulty
OFF
ON
*2: Dimly lit or blinks.
6 - 18
This test allows you to check if the module itself operates normally or not.
Follow the steps shown below.
Connect cable and supply 24V DC through
dedicated power supply or power supply
adapter
Before power ON, check the following:
Installed condition of module
Voltage input from power supply
"Stop" position of RUN/STOP switch of
CPU module
"Central position" of RESET switch of CPU
module
*1
Turn "ON" SW8 of operation setting switch
of QJ61CL12 and set it to test mode.
Reset the CPU module by the following
procedure.
1) Set switch to RESET position.
2) Set switch to middle position.
LED Indication
ERR.
SD
RD
OFF
*2
*2
OFF
OFF
OFF
OFF
OFF
OFF
ON
OFF
OFF
Start
Power ON
RESET
RESET
END
[Test Results]
L RUN
L ERR.
ON
OFF
OFF
ON
Replace module because of faulty hardware
OFF
OFF
OFF
OFF
Set operation setting switch again.
MELSEC-Q
Corrective Action
6 - 18