Installing the isCon® system
WARNING
7 2
Note!
32 | DE
Fig 20:
Adjusting the stripping length
1. Using the stripping tool isCon stripper 2, adjust the stripping length to
25 mm.
Fig 21: Cutting the insulation
2. Insert the isCon
conductor into the cutting head and, with slight pres-
®
sure, turn the handle in a clockwise direction until the preset length of
the insulation has been cut off.
Risk of function loss!
If there is a lightning strike, connection faults can lead to devices being de-
stroyed, fires triggered and human lives being endangered.
After stripping, ensure an even cut edge.
Remove any excess by hand.
Mounting isCon connection elements
All the isCon connection elements are mounted according to the same
principle.
T he isCon ASE... connection elements must be checked with an insula-
tion measuring device for correct function before mounting:
– Insulation test at 500 V: Correct value ≥ GΩ
– Insulation test at 1,000 V: Correct value ≤ GΩ
25 mm
OBO Bettermann