WARNING Do not connect each line of F39-TGR-MCL_ system to a DC power supply of more than 24
VDC+20%. Also, do not connect to an AC power supply. Failure to do so may result in electric shock.
WARNING For the F39-TGR-MCL_ system to comply with IEC 61496-1 and UL 508, the DC power
supply unit must satisfy all of the following conditions:
- Must be within the rated power voltage (24 V DC ± 20%)
- Must have tolerance against the total rated current of devices if it is connected to multiple devices
- Must comply with EMC directives (industrial environment)
- Double or reinforced insulation must be applied between the primary and secondary circuits
- Automatic recovery of over-current protection characteristics
- Output holding time must be 200 ms or longer
- Must satisfy output characteristic requirements for class 2 circuit or limited voltage current circuit
defined by UL508
- Must comply with laws and regulations, regarding EMC and electrical equipment safety, of the country
or region where the F3S-TGR-CL system is used (Ex: In EU, the power supply must comply with the
EMC Directive and the Low Voltage Directive).
WARNING Double or reinforced insulation from hazardous voltage must be applied to all input and
output lines. Failure to do so may result in electric shock.
WARNING Extension of the cable must be within a specified length. If it isn't, safety function may not
work properly, resulting in danger.

2.4 Other

Do not try to disassemble, repair, or modify this product. Doing so may cause the safety
WARNING
functions to stop working properly.
Do not use the F39-TGR-MCL_ system in environments where flammable or explosive
WARNING
gases are present. Doing so may result in an explosion.
Perform daily and 6-monthly inspections for the F39-TGR-MCL_ system. Otherwise, the
WARNING
system may fail to work properly, resulting in serious injury.
If the F39-TGR-MCL_ system is used in an environment where foreign materials such as
WARNING
spatter may adhere to the product, use a cover to protect the F39TGR-MCL_ system or inspect and
clean the F39-TGR-MCL_ system periodically.
Do not use the F39-TGR-MCL_ system in an atmosphere containing oil mist or corrosive
WARNING
gas. Failure to do so may result in damage of the product.
When scrapping the F39-TGR-MCL_ system, please make sure to comply with the waste
WARNING
treatment regulations of the country where the product has been used.

2.5 Precautions for Safe Use

Make sure to observe the following precautions that are necessary for ensuring safe use of the product.
- Thoroughly read this manual and understand the installation procedures, operation check procedures, and
maintenance procedures before using the product.
- Do not drop the product
- Dispose of the product in accordance with the relevant rules and regulations of the country or area where the
product is used.

2.6 Precautions for Correct Use

Observe the precautions described below to prevent operation failure, malfunctions, or undesirable effects on
product performance.