5.3 Installation and selection of the activation sequence

Since the muting actuators can be either used in T- and L-muting, the activation sequence can be modified
according to the application using DIP-switches. Indicator LEDs on receiver of the F39-TGR-MCL – system and
on the transceiver of the F39-TGR-MCL-R – system show the status of the Muting signals MUT A and MUT B and
if OFF-delay is active. The LEDs are visible from the front side. They are located next to the endcap where the
DIP-switches are located.
Sensor 2
By default the Sensor 1 is linked to the MUT A signal output and Sensor 2 is linked to the MUT B signal output.
DIP switches are located at the end of the muting actuator under a removable cover.
DIP switches setting:
Note Incorrect setting of the DIP-switches may damage the muting actuator.
Indicator LEDs:
LED (red) POWER
LED (red) Status MUT A
LED (red) Status MUT B
LED (red) MUTING DISABLED
OFF-Delay setting
DIP switches
Indicator LEDs
Sensor 1 linked to
SW1 ON
SW2 ON
MUT A
SW3 OFF
signal output
SW4 OFF
SW1 OFF
SW2 OFF
MUT B
SW3 ON
signal output
SW4 ON
Sensor 1
Sensor 2 linked to
MUT B
signal output
MUT A
signal output
OFF-Delay setting
DIP switches
Indicator LEDs
12