4.9 Objects "Threshold"

NO.
Object name
25
Output N
If this communication object is activity , the input value of receiving telegram from bus compare with
threshold 1 and threshold 2 calculate the state of switch according to the setting of database.
26
Output N
Change threshold1 value via bus.
27
Output N
Change threshold2 value via bus.
......

4.10 Objects "Heating"

1 bit heating control
1 byte heating control
NO.
Object
name
28
Output N
If work in heating actuator, this communication object default show and valid. Start PWM by receive
telegram "1",stop PWM by receive telegram "0" , start running automatic when power on set by ETS
28
Output N
If select "heat with byte control", this communication object has been showed and valid. Can modify
value of PWM by receive 1byte data. output ON always if receive value is 255 , output OFF if receive
value is 0, otherwise output PWM according to the value of receiving telegram from bus.
......
Function
Threshold input
Change threshold 1
Change threshold 2
Function
Heat with 1bit control
Heat with 1byte control
DimME KNX
Flags
C W U
C W U
C W U
Flags
C W U
C W U
Data type
DPT 5.004
1byte
DPT 5.004
1byte t
DPT 5.004
1byte
Data type
DPT1.001
1bit
DPT 5.004
1byte
32/35