Eternus Dx Installation; Installation Specifications; Eternus Dx8100 S4; Table 1 Eternus Dx8100 S4 Installation Specifications - Fujitsu ETERNUS DX8100 S4 Site Planning Manual

Hybrid storage systems
Table of Contents

Advertisement

1.

ETERNUS DX Installation

This chapter provides the installation specification of the ETERNUS DX.

Installation Specifications

ETERNUS DX8100 S4

The following table shows the installation specifications of the ETERNUS DX8100 S4.
Table 1
ETERNUS DX8100 S4 Installation Specifications
Item
Dimensions
(W ´ D ´ H)
Maximum weight
Power
Maximum power
consumption
Maximum heat
generation
Maximum amount
of exhaust air
Controller enclosure
Drive enclosure
Power distribution unit
Controller enclosure
Drive enclosure (*1)
Power distribution unit
Controller enclosure
Drive enclosure
2.5" type
(*1)
Controller enclosure
Drive enclosure
2.5" type
(*1)
Controller enclosure
Drive enclosure (*1)
ETERNUS DX8100 S4
482 ´ 788 ´ 133mm (3U)
482 ´ 540 ´ 88mm (2U)
2.5" type
485 ´ 123 ´ 44mm ´ 2 (2U)
AC200V
58kg
2.5" type
35kg
AC200V
3.0kg ´ 2
Voltage
AC 200 – 240V
Phase
Single
Frequency
50Hz/60Hz
AC 200 – 240V
1,100W (1,120VA)
AC 200 – 240V
430W (440VA)
AC 200 – 240V
3,960kJ/h
AC 200 – 240V
1,600kJ/h
3
6.2m
/min
2.5" type
3
4.0m
/min
9
Site Planning Guide

Advertisement

Table of Contents
loading

This manual is also suitable for:

Eternus dx8900 s4

Table of Contents