OPERATION
6

6.3.3 How to get access to the Quick Setup menu

The Quick Setup menu contains the menu items that are necessary for most configurations of
the device. The menu items are divided into 2 groups: "Standard Setup" and "Empty Spectrum".
The "Standard Setup" group lets the user (with "Expert" access level) set the tank height, tank
type (process, storage etc.), output variable, output current range, 0% range, 100% range, error
function and error delay. "Empty Spectrum" is a procedure that finds interference signals in the
tank and uses a filter to remove them from the measurement data.
CAUTION!
If you did not supply all installation data to the supplier before the delivery, the standard setup
procedure in the Quick Setup menu is mandatory.
Do the steps that follow:
• Push [>] to enter Program mode.
• Push [>], 2 × [ ▼ ] to go to the menu item A3 Login.
• Push [>]. Enter the password used at this time for the "Expert" access level. If it is the default
password, enter "0058".
• Push [ ↲ ], [ ▼ ] and [>] to go to the menu item A4.1 Standard Setup.
• Push [>]. Do the basic configuration of the device in the "Standard Setup" menu. For more data
on the procedure, refer to Standard setup on page 90. Push [ ↲ ] at the end of each step of the
procedure to continue to the next step.
• Push [ ▼ ] and [>] to go to the menu item A4.2.1 Record Spectrum.
• Push [>] to start the empty spectrum recording procedure. For more data, refer to Empty
spectrum recording on page 93. Push [ ↲ ] at the end of each step of the procedure to continue
to the next step.
• End of the procedure.