PROFIBUS SETTINGS

4
Detailed description of special settings concerning the PROFIBUS features easily operated via
the local display menu of the signal converter (refer to the following sections). For a detailed
description of the menus and functions in general please refer to the standard product
documentation of the signal converter.

4.1 Menu "A Quick Setup"

Function
A14 Identification Number
A15 Station Address
A12.15 Cluster 15
A15.15.1 FB Analog Output Unit
A15.15.2 FB Totalizer 1 Unit
A15.15.3 FB Totalizer 2 Unit
Table 4-1: Description of menu "A Quick Setup"

4.2 Menu "B Test"

Function
B2 Actual Values
B2 Actual Values
B2 Actual Values
B2 Actual Values
B2.22 FB Analog Input 1
B2.23 FB Analog Input 2
B2.24 FB Analog Input 3
B2.25 FB Analog Input 4
B2.26 FB Analog Input 5
B2.27 FB Totalizer 1
B2.28 FB Totalizer 2
Table 4-2: Description of menu "B Test"

4.3 Menu "C Setup"

Function
C3 Communications
C3 Communications
C3 Communications
C3 Communications
C3.3 Profibus PA
C3.3.1 Physical Block
C3.3.1.1 Tag
C3.3.1.2 Identification Number
C3.3.1.3 Station Address
C3.3.2 TB Flow
C3.3.2.1 Low Flow Cutoff
C3.3.2.2 LFC Hysteresis
32
Setting / Description
Unique Profibus ID number
Profibus station address
Menu listing all Profibus unit settings related to cluster check 15
Select Analog Output unit (cf. C3.3.8.2)
Select Totalizer 1 unit (cf. C4.3.4)
Select Totalizer 2 unit (cf. C4.4.4)
Setting / Description
Displays current value of Analog Input 1
Displays current value of Analog Input 2
Displays current value of Analog Input 3
Displays current value of Analog Input 4
Displays current value of Analog Input 5
Displays current value of Totalizer 1
Displays current value of Totalizer 2
Setting / Description
Profibus configuration submenu.
Description of the physical block.
Tag of the device.
Setting:
Profile: Profile specific identification number (9741 hex);
Manufacturer: Manufacturer specific identification number (4541 hex);
Automatic: Automatic adaptation mode
Selects the address of the device at the PROFIBUS interface.
Transducer Block configuration submenu.
The volume flow and further measuring values are set to zero if its absolute
value is less than the "Low Flow Cutoff" value.
Defines the hysteresis used during calculation of the volume flow "Low Flow
Cutoff" function.
www.krohne.com
06/2019 - 4005059401 - AD VFC200 PB-PA R01 en