Function Tables; Menu "Quick Setup - KROHNE MFC 400 Manual

Signal converter for mass flowmeters
Hide thumbs Also See for MFC 400:
Table of Contents

Advertisement

MFC 400

6.3 Function tables

INFORMATION!
The following tables describe the functions of the standard device with HART
The functions for Modbus, Foundation Fieldbus and Profibus are described in detail in the
corresponding supplementary instructions.
Depending on the device version, not all functions are available.
The device provides an expert mode. Some functions marked with * are only available in
expert mode.

6.3.1 Menu "Quick Setup"

Function
A0.0.0 Quick Setup
A0.0.0 Quick Setup
A0.0.0 Quick Setup
A0.0.0 Quick Setup
A1.0.0 Language
A1.0.0 Language
A1.0.0 Language
A1.0.0 Language
A2.0.0 Reset
A2.0.0 Reset
A2.0.0 Reset
A2.0.0 Reset
A2.1.0 Reset Errors
A2.2.0 Stop all Simulations
A2.3.0 All Totalisers
A2.4.0 Totaliser 1
A2.5.0 Totaliser 2
A2.6.0 Totaliser 3
A3.0.0 Configuration
A3.0.0 Configuration
A3.0.0 Configuration
A3.0.0 Configuration
A3.1.0 Tag
A3.2.0 Measurement
A3.3.0 Range
A3.4.0 Alarm Code
A3.5.0 Low Flow Cutoff
07/2016 - 4002075804 - MA MFC 400 R04 en
Description and selection
Select language.
Available languages: English, German, French, Danish, Spanish, Italian,
Dutch, Polish, Portuguese, Swedish, Turkish
Reset Errors?
Select: No / Yes
Stop all running simulations?
Select: No / Yes
Reset all Totalisers?
Select: No / Yes
Reset Totaliser 1?
Select: No / Yes
Reset Totaliser 2?
Select: No / Yes
Reset Totaliser 3?
Select: No / Yes
Safety relevant parameters for SIL setup.
Measuring point identifier (Tag no.) (also for HART
displayed in the LCD header (max. 8 digits).
Measurement value for current output at terminals C.
Select: Flow Velocity / Volume Flow / Mass Flow / Temperature / Density /
Sensor Average / Sensor Deviation / Drive Level / Tube Frequency /
Strain 1 / Strain 2 / 2 Phase Signal
Depending on the settings for the concentration measurement, the following
measurements are possible:
Concentration 1 / Concentration 2 / Conc. mass flow 1 / Conc. mass flow 2 /
Conc. volume flow 1 / Conc. volume flow 2
Range setting for current output.
Selection depends on the measurement value.
Specify the failure current output.
Select: Low (3.5 mA) / High (21.5 mA)
Sets the measurement to "0" for low values.
x.xxx ± x.xxx%; range: 0.0...20%
(1st value = switching point / 2nd value = hysteresis);
condition: 2nd value ≤ 1st value
www.krohne.com
OPERATION
6
®
connection.
®
operation) will be
61