4.2.3. Inserting Float-type Variables into a Message

The iKAN display device provides Modbus registers for 64 float variables, allowing the Host PC or
a PLC to read or write data via the Modbus TCP/ RTU protocol. These values can also be inserted
into a message. If these values are modified via a remote Host or a PLC, the value will be
automatically refreshed when it is displayed on the iKAN series device.
The format for using a variable in a message is a 5-byte string, as follows:
1
Delimiter
Variable Type
Character
%
f: Float variable (-3.4E+38 to +3.4E+38)
A maximum of 64 float variables can be stored on the iKAN series device, and are accessed using
Modbus register addresses 40128 to 40254.
Modbus Address
Length
Decimal
Hex.
40128
0080
:
:
40255
00FF
iKAN Series Display User Manual
2
Description
64
Float-type variables
3 to 5
Modbus Address:
3-digit decimal number
X
X
Value Range
3.4E+38 to +3.4E+38
v 1.1.0