Endress+Hauser HART iTEMP TMT182B Operating Instructions Manual page 40

Temperature transmitter

Advertisement

Technical data
Standard
Designation
OIML R84: 2003, GOST
Cu50 (14)
6651-94
Resistance
Resistance Ω
transmitter
1)
Measured value transmitted via HART
2)
Percentages based on the configured span of the analog output signal.
3)
Deviations from maximum measured error possible due to rounding.
Measured error for thermocouples (TC) and voltage transmitters
Standard
Designation
Type A (30)
IEC 60584-1
ASTM E230-3
Type B (31)
IEC 60584-1
ASTM E230-3
Type C (32)
ASTM E988-96
ASTM E988-96
Type D (33)
Type E (34)
Type J (35)
Type K (36)
IEC 60584-1
ASTM E230-3
Type N (37)
Type R (38)
Type S (39)
Type T (40)
Type L (41)
DIN 43710
Type U (42)
GOST R8.585-2001
Type L (43)
Voltage transmitter
(mV)
1)
Measured value transmitted via HART
2)
Percentages based on the configured span of the analog output signal.
3)
Deviations from maximum measured error possible due to rounding.
40
Measuring range
–50 to +200 °C (–58 to +392 °F)
10 to 400 Ω
10 to 2 850 Ω
®
.
Measuring range
0 to +2 500 °C (+32 to +4 532 °F)
+500 to +1 820 °C
(+932 to +3 308 °F)
0 to +2 000 °C (+32 to +3 632 °F)
–150 to +1 000 °C
(–238 to +1 832 °F)
–150 to +1 200 °C
(–238 to +2 192 °F)
–150 to +1 300 °C
(–238 to +2 372 °F)
+200 to +1 768 °C
(+392 to +3 214 °F)
–150 to +400 °C (–238 to +752 °F) ME = ± (0.5 °C (0.9 °F) - 0.05% * (MV - LRV))
–150 to +900 °C
(–238 to +1 652 °F)
–150 to +600 °C
(–238 to +1 112 °F)
–200 to +800 °C
(–328 to +1 472 °F)
–20 to +100 mV
®
.
Total measured error of transmitter at current output = √(Measured error digital² +
Measured error D/A²)
Measured error (±)
Digital
ME = ± (0.12 °C (0.22 °F) + 0.004% * (MV - LRV))
ME = ± 25 mΩ + 0.0032 % * MV
ME = ± 120 mΩ + 0.006 % * MV
Measured error (±)
Digital
3)
Based on measured value
ME = ± (1.25 °C (2.25 °F) + 0.026% * (MV - LRV))
ME = ± (2.25 °C (4.05 °F) - 0.09% * (MV - LRV))
ME = ± (1.15 °C (2.07 °F) + 0.0055% * (MV - LRV))
ME = ± (1.25 °C (2.25 °F) - 0.016% * (MV - LRV))
ME = ± (0.4 °C (0.72 °F) - 0.008% * (MV - LRV))
ME = ± (0.45 °C (0.81 °F) - 0.007% * (MV - LRV))
ME = ± (0.6 °C (1.08 °F) - 0.01% * (MV - LRV))
ME = ± (0.8 °C (1.44 °F) - 0.025% * (MV - LRV))
ME = ± (1.6 °C (2.88 °F) - 0.025% * (MV - LRV))
ME = ± (1.6 °C (2.88 °F) - 0.025% * (MV - LRV))
ME = ± (0.5 °C (0.9 °F) - 0.016% * (MV - LRV))
ME = ± (0.55 °C (0.99 °F) - 0.04% * (MV - LRV))
ME = ± (2.45 °C (4.41 °F) - 0.015% * (MV - LRV))
ME = ± 10.0 µV
iTEMP TMT182B
1)
D/A
0.03 % (
4.8 µA)
1)
D/A
0.03 % (
4.8 µA)
0.03 % (
4.8 µA)
4.8 µA