iTEMP TMT182B
Endress+Hauser
Diagnostic
Short text
number
411
Up-/download active
435
Linearization faulty
485
Process variable
simulation active
491
Output simulation
495
Diagnostic event
simulation active
531
Factory adjustment
missing
537
Configuration
537
Configuration
582
Sensor diagnostics TC
deactivated
Diagnostic of process
801
Supply voltage too low
825
Operating temperature
844
Process value out of
specification
9.5
Event logbook
Previous diagnostic messages are displayed in the Event logbook submenu.
9.6
Firmware history
Revision history
The firmware version (FW) on the nameplate and in the Operating Instructions indicates
the device release: XX.YY.ZZ (example 01.02.01).
XX
Change to main version. No longer compatible. The device and
Operating Instructions change.
YY
Change to functions and operation. Compatible. The Operating
Instructions change.
ZZ
Fixes and internal changes. No changes to the Operating Instructions.
Date
Firmware version
12/2022
01.01.zz
10
Maintenance
No special maintenance work is required for the device.
Remedy instructions
Up-/download in progress,
please wait
Check linearization
Deactivate simulation
Deactivate simulation
Deactivate simulation
1. Contact service organization
2. Replace device
1. Check device configuration
2. Up- and download new
configuration
Check current output
configuration
Switch on diagnostics for
thermocouple measurement
Increase supply voltage
1. Check ambient temperature
2. Check process temperature
1. Check process value
2. Check application
3. Check sensor
Changes
Documentation
Original firmware
BA02260T, Version 01.22
Maintenance
Status signal
Diagnostic
[from the
behavior
factory]
[from the
factory]
C
Warning
F
Alarm
C
Warning
C
Warning
C
Warning
F
Alarm
F
Alarm
F
Alarm
C
Warning
S
Alarm
S
Warning
S
Warning
31