Endress+Hauser HART iTEMP TMT182B Operating Instructions Manual page 39

Temperature transmitter

Advertisement

iTEMP TMT182B
Refresh time
Reference operating
conditions
Maximum measured error
Typical
Standard
Resistance thermometer (RTD) as per standard
IEC 60751:2008
IEC 60751:2008
GOST 6651-94
Thermocouples (TC) as per standard
IEC 60584, Part 1
IEC 60584, Part 1
GOST R8.585-2001
1)
Measured value transmitted via HART
Measured error for resistance thermometers (RTD) and resistance transmitters
Standard
Designation
Pt100 (1)
Pt200 (2)
IEC 60751:2008
Pt500 (3)
Pt1000 (4)
JIS C1604:1984
Pt100 (5)
Pt50 (8)
GOST 6651-94
Pt100 (9)
Ni100 (6)
DIN 43760 IPTS-68
Ni120 (7)
Cu50 (10)
Cu100 (11)
OIML R84: 2003 /
GOST 6651-2009
Ni100 (12)
Ni120 (13)
Endress+Hauser
Approx. 100 ms
• Calibration temperature: +25 °C ±3 K (77 °F ±5.4 °F)
• Supply voltage: 24 V DC
• 4-wire circuit for resistance adjustment
In accordance with DIN EN 60770 and the reference conditions specified above. The
measured error data correspond to ±2 σ (Gaussian distribution). The data include non-
linearities and repeatability.
MV = Measured value
LRV = Lower range value of relevant sensor
Designation
Pt100 (1)
Pt1000 (4)
Pt100 (9)
Type K (NiCr-Ni) (36)
Type S (PtRh10-Pt) (39)
0 to +800 °C (32 to +1 472 °F)
Type L (NiCr-CuNi) (43)
®
.
Measuring range
–200 to +850 °C
(–328 to +1 562 °F)
–200 to +510 °C (–328 to +950 °F) ME = ± (0.1 °C (0.18 °F) + 0.008% * (MV - LRV))
–200 to +250 °C (–328 to +482 °F) ME = ± (0.06 °C (0.11 °F) + 0.007% * (MV - LRV))
–200 to +510 °C (–328 to +950 °F) ME = ± (0.08 °C (0.14 °F) + 0.006% * (MV - LRV))
–185 to +1 100 °C
(–301 to +2 012 °F)
–200 to +850 °C
(–328 to +1 562 °F)
–60 to +250 °C (–76 to +482 °F)
–180 to +200 °C (–292 to +392 °F) ME = ± (0.12 °C (0.22 °F) + 0.006% * (MV - LRV))
–180 to +200 °C (–292 to +392 °F) ME = ± (0.08 °C (0.14 °F) + 0.003% * (MV - LRV))
–60 to +180 °C (–76 to +356 °F)
Measuring range
0 to +200 °C (32 to +392 °F)
Based on measured value
ME = ± (0.1 °C (0.18 °F) + 0.006% * (MV - LRV))
ME = ± (0.2 °C (0.36 °F) + 0.011% * (MV - LRV))
ME = ± (0.13 °C (0.23 °F) + 0.008% * (MV - LRV))
ME = ± (0.08 °C (0.14 °F) + 0.0055% * (MV - LRV))
ME = ± (0.08 °C (0.14 °F) - 0.004% * (MV - LRV))
ME = ± (0.08 °C (0.14 °F) - 0.004% * (MV - LRV))
Typical measured error (±)
1)
Digital value
0.12 °C (0.22 °F)
0.09 °C (0.16 °F)
0.10 °C (0.18 °F)
1)
Digital value
0.65 °C (1.17 °F)
1.50 °C (2.70 °F)
2.60 °C (4.68 °F)
Measured error (±)
1)
Digital
3)
Technical data
Value at current
output
0.14 °C (0.25 °F)
0.11 °C (0.20 °F)
0.12 °C (0.22 °F)
Value at current
output
0.69 °C (1.24 °F)
1.52 °C (2.74 °F)
2.61 °C (4.70 °F)
2)
D/A
0.03 % (
4.8 µA)
0.03 % (
4.8 µA)
39