iTEMP TMT182B
Endress+Hauser
Structure of thermometer with RTD sensors and head transmitter:
1. Fit the thermowell (1) on the process pipe or the container wall. Secure the
thermowell according to the instructions before the process pressure is applied.
2. Fit the necessary neck tube nipples and adapter (3) on the thermowell.
3. Make sure sealing rings are installed if such rings are needed for harsh
environmental conditions or special regulations.
4. Guide the mounting screws (6) through the side boreholes of the head transmitter
(5).
5. Position the head transmitter (5) in the terminal head (4) in such a way that the
power supply lines (terminals 1 and 2) point to the cable entry.
6. Using a screwdriver, screw down the head transmitter (5) in the terminal head (4).
7. Guide the connection wires of the insert (3) through the lower cable entry of the
terminal head (4) and through the middle hole in the head transmitter (5). Wire the
connection wires up to the transmitter .
8. Screw the terminal head (4), with the integrated and wired head transmitter, onto
the ready-mounted nipple and adapter (3).
NOTICE
The terminal head cover must be secured properly to meet the requirements for
explosion protection.
After wiring, securely screw the terminal head cover back on.
4.3
Post-mounting check
After installing the device, carry out the following checks:
Device condition and specifications
Are the device, the connections and connecting cables free of damage (visual
inspection)?
Do the ambient conditions match the device specification (e.g. ambient temperature,
measuring range, etc.)?
Have connections been established correctly and with the specified torque?
Mounting
Notes
-
See the ' T echnical
data' section
-
11