Follow the guidelines below when wiring the module.
General
Power and input wiring must be in accordance with Class 1, Division 2 wiring
methods, Article 501-4(b) of the National Electric Code, NFPA 70, and in
accordance with the authority having jurisdiction.
Channels are isolated from one another by 500V dc maximum.
Route field wiring away from any other wiring and keep it as far as possible
from sources of electrical noise, such as motors, transformers, contactors, and ac
devices. As a general rule, allow at least 15.2 cm (6 in.) of separation for every
120V of power.
Routing field wiring in a grounded conduit can reduce electrical noise.
If field wiring must cross ac or power cables, ensure that they cross at right
angles.
If multiple power supplies are used with analog millivolt inputs, the power
supply commons must be connected.
To ensure optimum accuracy, limit overall cable impedance by keeping a cable
as short as possible. Locate the module as close to input devices as the
application permits.
Grounding
This product is intended to be mounted to a well-grounded mounting surface
such as a metal panel. Additional grounding connections from the module's
mounting tabs or DIN rail (if used) are not required unless the mounting surface
cannot be grounded.
Keep cable shield connections to ground as short as possible.
Ground the shield drain wire at one end only. The preferred location is as
follows.
For grounded thermocouples or millivolt sensors, this is at the sensor
o
end.
For insulated/ungrounded thermocouples, this is at the module end.
o
Contact your sensor manufacturer for additional details.
Refer to Industrial Automation Wiring and Grounding Guidelines, Allen-
Bradley publication 1770-4.1, for additional information.
RTD Wiring Considerations
The module requires three wires to compensate for lead resistance error.
If using a 3-wire configuration for module connections, select cable to ensure
that lead wire resistances match as closely as possible. Consider the following:
To ensure temperature or resistance value accuracy, the resistance
o
difference of the cable lead wires must be less than or equal to 0.01 Ω .