Note: For the MSTP connection, Port 1 is supported. Port 2 does not support BACnet MSTP. EasyIO FS
series is not a BBMD Device nor BACnet Router. The FS BACnet service can register itself to a BBMD device
to receive broadcast messages through the bbmdEnable, bbmdIp, and bbmdTTL properties. If BBMD is not
preset or required in the network, these properties must be blank. If the communications stack is
configured correctly, the status displays OK.
6. To view the property on the property sidebar, click the Server Network object and enable the server
network. If the IP service and MSTP service are enabled correctly for the BACnet Service object, the status
displays OK.
7. Drag the BACServerBV, BACServerAV, BACServerMSV, BACServerTrend, or BACSchedule type object under
the Network object. The register object must be a child folder of the network object.
Note: The BACnet server and BACnet client object can coexist under the BACnet service object. There can
only be one BACnet service object in a controller. No duplicate BACnet service object is allowed.