Connecting-Up - Siemens SIMOVERT FC Operating Instructions Manual

Master drives, chassis units (types e - h)
Table of Contents

Advertisement

08.96
3

Connecting-up

SIMOVERT MASTER DRIVES are operated at high voltages.
The equipment must be in a no-voltage condition (disconnected from the supply) before any
work is carried-out!
Only professionally trained, qualified personnel must work on or with the unit.
Death, severe bodily injury or significant material damage could occur if these warning
instructions are not observed.
Extreme caution should be taken when working-on the unit when it is open, as external
power supplies may be connected. The power terminals and control terminals can still be at
hazardous potentials even when the motor is stationary.
Hazardous voltages are still present in the unit up to 5 minutes after it has been powered-
down due to the DC link capacitors. Thus, the appropriate delay time must be observed
before opening-up the unit.
Forming the DC link capacitors:
The storage time should not exceed one year. The converter DC link capacitors must be
formed at start-up if the unit has been stored for a longer period of time.
Forming is described in the Instruction Manual, Part 2.
The user is responsible, that the motor, converter and any other associated devices or units
are installed and connected-up according to all of the recognized regulations in that
particular country as well as other regionally valid regulations. Cable dimensioning, fusing,
grounding, shutdown, isolation and overcurrent protection should be especially observed.
If a protective device trips in a current arm, then a fault current could have been interrupted.
In order to reduce the danger of fire or electric shock, the live parts and over components of
the converter should be checked and damaged components replaced.
♦ Protection:
Fuses must be incorporated in the equipment supply connection. For a list of the
recommended fuses, refer to Table 3.1.
♦ Supply rating: The converter is suitable for connecting to supplies with a short-circuit rating (supply) ≤ 100 ×
rated output (converter).
♦ The converter should be connected via a line reactor according to Table 3.1.
♦ Cabling/wiring: Connecting cables should be dimensioned according to the local regulations and according
to Table 3.1. The insulation should be suitable for 75 °C.
Siemens AG
6SE7087-6AH70
SIMOVERT MASTER DRIVES
INFORMATION
Operating Instructions
WARNING
Connecting-up
3-1