The specified lengths are valid for unshielded cables; for shielded cables, the values must be reduced to 2/3.
If several motors are connected to a drive converter, the sum of the cable lengths of all of the motor feeder
cables must be less than the permissible cable lengths.
When fully utilizing the permissible cable lengths, a line commutating reactor should be used and, if required, a
higher starting current set.
6.5.1.4

Selection criteria for the output reactor, dv/d filter or sinusoidal filter

The following table indicates the selection criteria for the output reactor,dv/dt filter or sinusoidal filters
Motors, acc. to
dv/dt filter or sinusoidal filter
IEC 34-17:1992
required!
(DIN VDE 0530,
Cable lengths in accordance
Part 1, Sheet 2)
with the Section „dv/dt filter",
Fig. 6.5 and Section
„Sinusoidal filter", Fig. 6.6.
Siemens motors
An output filter is not
required.
1LA2,
For longer motor cable
1LA5,
lengths, output reactors are
1LA6,
required in accordance with
*)
1LA8
.
Section „Output reactor", Fig.
6.4.
*) Standard 1LA8 motors; 1LA8 motors are available with a better insulation.
Table 6.10
Selection criteria for the following options: Output reactor, sinusoidal filter and dv/dt filter between the converter and motor
Siemens AG
6SE7087-6AH70
SIMOVERT MASTER DRIVES
380 V - 500 V (3AC)
Operating Instructions
NOTE
Voltage range
525 V - 575 V (3-ph. AC)
dv/dt filter or sinusoidal filter
required!
Cable lengths in accordance
with the Section „dv/dt filter",
Fig. 6.5 and Section
„Sinusoidal filter", Fig. 6.6.
dv/dt filter or sinusoidal filter
required!
Cable lengths in accordance
with the Section „dv/dt filter",
Fig. 6.5 and Section
„Sinusoidal filter", Fig. 6.6.
660 V - 690 V (3AC)
dv/dt filter required!
Cable lengths in accordance
with the Section „dv/dt filter",
Fig. 6.5.
dv/dt filter required!
Cable lengths in accordance
with the Section „dv/dt filter",
Fig. 6.5.
Options
6-9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Simovert vcSimovert sc

Table of Contents