Parameter
Use MI as measuring
input
Use DR as Drive Ready
Input delay
Tolerated number of
sign-of-life errors
4.3

Address space

Address space of the technology module
Table 4- 2
Range per channel
Total range
Additional information
For a description of the control and feedback interface of the technology module, see section
Control and feedback interface (Page 30).
Technology module TM PTO 2x24V (6ES7138‑6EB00‑0BA0)
Equipment Manual, 09/2021, A5E50983437-AA
Description
Enables use of the measuring input signal at the Digital input MI (Page 17).
You can save the current position of the drive axis using the measuring
input signal with the technology object TO_MeasuringInput.
Enables use of the ready signal of the drive at Digital input DR (Page 17).
Selection of the input delay for the signal at the respective digital input for
noise suppression. Changes to the signal are only detected if they remain
stable for longer than the configured input delay time.
The input delay applies to all the used hardware inputs of the channel.
Input of how many Master Sign-Of-Life errors are tolerated by the module.
If the number is exceeded, this triggers an error message via return bit
(Page 34) Sensor_Error.
65535 means: No monitoring for sign-of-life errors
Range of the input addresses and output addresses of the TM PTO 2x24V
Inputs
16 bytes
32 bytes
Configuring/address space
4.3 Address space
Outputs
8 bytes
16 bytes