Diagnostic alarms
The diagnostics are displayed as plain text in STEP 7 (TIA Portal) in the online and diagnostics
view. You can evaluate the error codes with the user program. The respective channel
number is shown for each diagnostic information.
The following diagnostics can be signaled:
Table 5- 5
Diagnostic alarms, their meaning and remedies
Diagnostic alarm
Error
code
Error
9
H
Parameter assign-
10
H
ment error
Supply voltage
11
H
missing
Channel
1F
H
/component tem-
porarily unavaila-
ble
Error at the digital
10F
outputs
1,2
The digital outputs CH0.ED and CH1.ED have common diagnostics.
1
The module detects short-circuit and overload up to an output frequency of approx. 50 kHz and at a pulse width > 10 µs.
2
No diagnostics are output for higher frequencies. However, the module is protected against destruction by short-circuits
at the outputs in any case.
The pulse width is fixed depending on the maximum pulse frequency set for the respective channel. The maximum pulse
frequency depends, for example, on the signal evaluation and the number of increments per revolution.
Technology module TM PTO 2x24V (6ES7138‑6EB00‑0BA0)
Equipment Manual, 09/2021, A5E50983437-AA
Meaning
Internal module error occurred
Possible cause:
Firmware update was aborted
Technology module defective
The received parameter data record is invalid
The configured BaseUnit is not the BaseUnit
being used
No or insufficient supply voltage L+
Possible cause:
Wiring of supply voltage L+ faulty
BaseUnit type wrong
Firmware update is in progress or has been
aborted. The module reads no process values in
this state.
Error at the digital outputs
H
Possible causes:
Short-circuit
Overload
Interrupts/diagnostic alarms
5.2 Diagnostic alarms
To correct or avoid errors
Repeat firmware update
Replace technology module
Check parameter data record
Check BaseUnit
Check BaseUnit type
Check supply voltage L+ at the Ba-
seUnit
Check wiring of supply voltage L+
Check total consumption of the load
group
Wait for firmware update.
If firmware update aborts:
Check minimum firmware version
required
Check the supply voltage
Repeat firmware update
Correct wiring at the digital outputs
Check consumers connected to the
digital outputs
45