Downloading system prints to a laptop

About this task:
Downloading system histories to a file is another useful method to capture system operating
conditions. The following instructions are used to establish communication between the
OptiView Control Panel and a laptop computer running any Terminal Emulation program such as
HyperTerminal, TeraTerm, or PuTTy.
1.
Connect the laptop computer to the OptiView as described below. If your computer does not
have a RS-232 serial port, you will need a USB to serial converter such as the Digi Edgeport/1.
Table 10: Laptop connection
Laptop (RS-232 Serial Port)
Pin
2
4
5
On the OptiView Printer Screen, select PC. This will allow faster data download than the
2.
printer selections. SETTINGS should match the Port settings below.
3.
Set up the Terminal Emulation program.
a.
Set the Com port for the port that the USB/Serial adapter is installed on.
b.
Set the Com port communication parameters as follows:
Table 11: Com port parameters
Field
Bits per second (Baud Rate)
Data bits
Parity
Stop Bits
Flow control
If DTR/DSR is used, set to Hardware.
If no DTR/DSR, set to None.
4.
Set the Terminal program to capture a file, and select the location and enter a file name.
5.
Press the Print Screen key on the appropriate screen to be captured. The HyperTerminal will
display the printed information and the information will be recorded as a .txt file.
Note: Since the menu options of the various Terminal Emulation programs are different,
the user will need to determine the exact steps required to save a file to their PC using
the desired program.
What to do next:
The following additional RS232 connections are used to wire up serial devices for desktop and
laptop computers.
Table 12: RS-232 pin assignments - DB25 PC signal set (older desktops only)
Pin
Pin 1
Protective Ground
Pin 3
Received Data
Pin 5
Clear To Send
Pin 7
Signal Ground
Pin 20
Data Terminal Ready
52
Description
RX
DTR
GND
Value
57600
8
None
1
None
Description
OptiView (Com 1)
Connector
to
J2
to
J2
to
J2
Pin
Description
Pin 2
Transmit Data
Pin 4
Request To Send
Pin 6
Data Set Ready
Pin 8
Received line Signal Detector (Data Carrier
Detect)
Pin 22
Ring Indicator
Model YD Mod D with OptiView Control Center
Terminal
4 (TXD1)
2 (DSR1)
8 GND

Advertisement