Johnson Controls York YD Manual page 41

Centrifugal liquid chillers
Hide thumbs Also See for York YD:
Table of Contents

Advertisement

Table 8: Cycling shutdown messages
Message
Motor Controller #2 –
Loss Of Current
Motor Controller #1 –
Power Fault
Motor Controller #2 –
Power Fault
Leaving Chilled Liquid
– Low Temperature
Control Panel –
Schedule
Oil Pump #1 – Drive
Contacts Open
Model YD Mod D with OptiView Control Center
Description
The chiller (both compressors 0 shutdown because compressor #2 motor current has
decreased to < 10% FLA for 25 continuous seconds while it was running. This could be caused
by the starter de-energizing or a defect in the motor current detection circuitry to the control
center. The motor current value is provided by CM-2 board 2 to the microboard. The chiller
will automatically restart at the completion of coastdown.
A motor controller protection device has shutdown the chiller (both compressors). Normally
closed contacts of locally installed external motor protection devices (connected between
TB6-15 and TB6-53) and the normally closed CM contacts of CM-2 Board 1 (connected
between TB6-53 and TB6-16) form a safety circuit in series with the starter run signal. If any
of these contacts open and reclose in less than 3 seconds, this shutdown is initiated. The
CM-2 board opens its contacts and recloses them in less than 3 seconds when it detects a
motor current power fault condition on motor #1. A power fault condition occurs when the
motor current drops below 10% FLA. This protects against potential compressor damage
due to rapid opening and reclosure of the motor starter. When it detects this condition,
the power fault LED on the CM-2 board lights and the board's CM contacts open and
automatically reclose in less than 3 seconds to initiate the shutdown. The LED will remain
lit until the reset button on the CM-2 board is pressed. The chiller will automatically restart
when at the completion of coastdown.
A motor controller protection device has shutdown the chiller (both compressors). Normally
closed contacts of locally installed external motor protection devices (connected between
TB6-15 and TB6-54) and the normally closed CM contacts of CM-2 Board 2 (connected
between TB6-54 and TB6-82) form a safety circuit in series with the starter run signal. If any
of these contacts open and reclose in less than 3 seconds, this shutdown is initiated. The
CM-2 board opens its contacts and recloses them in less than 3 seconds when it detects a
motor current power fault condition on motor 2. A power fault condition occurs when the
motor current drops below 10% FLA. This protects against potential compressor damage
due to rapid opening and reclosure of the motor starter. When it detects this condition,
the power fault LED on the CM-2 board lights and the board's CM contacts open and
automatically reclose in less than 3 seconds to initiate the shutdown. The LED will remain
lit until the reset button on the CM-2 board is pressed. The chiller will automatically restart
when at the completion of coastdown.
The chiller (both compressors) has shutdown because the leaving Chilled Liquid
Temperature has decreased to the programmed Shutdown Temperature setpoint. If the
chiller is running when this occurs, the pre-rotation vanes on the running compressors are
driven fully closed prior to shutting down the chiller. The chiller will automatically restart
when the temperature increases to the programmed Restart Temperature setpoint.
The programmed Daily Schedule setpoint has shutdown the chiller (both compressors).
If the chiller is running when this occurs, the pre-rotation vanes on the running compressors
are driven fully closed prior to shutting down the chiller. The chiller will automatically restart
at the next scheduled start time.
The oil pump variable speed drive for compressor 1 has shutdown the chiller (both
compressors). It initiates this shutdown by opening its status contacts connected to the I/O
Board TB3-70. The drive initiates a shutdown anytime its internal protection circuits will not
permit the Drive to run. The contacts remain open until its internal protection circuits are
satisfied and any applicable manual resets are performed. Refer to YORK Variable Speed Oil
Pump Drive Service Manual 160.52-M2.
If compressor 1 is locked out using the Lockout key on the Capacity compressor cycling
screen, this fault does not cause compressor 2 to shutdown or prevent it from starting.
When this fault occurs on a locked-out compressor, it is displayed as a warning. This allows
the user to know that a fault exists on the locked-out compressor. The condition must be
corrected prior to the lockout being removed from the compressor. If it is not, the warning
condition will revert back to a shutdown as soon as the lockout is removed and will cause the
chiller to trip.