Printers; Printing Overview; Control Center Setup - Johnson Controls York YD Manual

Centrifugal liquid chillers
Hide thumbs Also See for York YD:
Table of Contents

Advertisement

Printers

Printing overview

A laptop computer can be connected to the Control Center's Microboard to capture the following
reports. The screen from which each report can be generated is listed in parenthesis.
Status - Present system parameters (Printer, Home).
Setpoints - Present programmed values of all setpoints (Printer, Setpoints).
Schedule - Present value of programmed daily schedule (Printer, Schedule).
Sales Order - Information about SALES ORDER Screen (Printer, Sales Order).
History - System parameters at the time of the last normal stop, last fault while running and
last 10 faults, whether running or not (Printer, History).
Cycling or Safety Shutdown Initiated Print - Snapshot of all system parameters at instant
of shutdown. Automatically occurs if printer is connected at time of shutdown.
Trend - Prints a snapshot of the existing TREND Screen data or prints new data collected after
the TREND PRINT key is pressed.
The laptop computer can be permanently connected to the Control Center or connected as
required to produce a report. If permanently connected, a DATA LOGGING feature can produce
a status report automatically, beginning at an Operator selected start time and occurring at an
Operator selected interval thereafter between 1 and 1440 minutes.
The following figures are examples of the different reports:
Status: Figure 7.
Setpoints: Figure 8.
Schedule: Figure 9.
Sales Order: Figure 10.
History: Figure 11.
Security Log: Figure 12.
Trend: Figure 13.
Custom screen: Figure 14.

Control center setup

Automatic data logging
Access level required: Operator
If automatic data logging is desired, a status report can be automatically printed at a specified
interval beginning at a specified time, using the PRINTER Screen. The interval is programmable
over the range of 1 minute to 1440 minutes in 1 minute increments. The first print will occur at
the programmed START time and occur at the programmed Output Interval thereafter. The time
remaining until the next print is displayed on the PRINTER Screen.
Automatic Printer Logging - Enables and disables automatic data logging.
Log Start Time - Enter the time the first print is desired.
Output Interval - Enter the desired interval between prints.
Model YD Mod D with OptiView Control Center