UL requirements

Before installing the product in an UL system, read and follow the UL requirements described
below.
Depending on the Host Management, the system consists of:
The Access Professional Edition (APE) 3.4 or 3.5 or Building Integration System (BIS) - Access
Engine (ACE) 4.5, or AMS 2.0 as the Host Management System. This is an Access Control (UL
294 ALVY) system. It consists of the following devices - all listed to UL 294:
Notice!
i
The use of the burglar alarm, panic hardware, and elevator control have not been evaluated
by UL.
For UL compliance, use only UL Listed 26-bit Wiegand format readers.
The following Bosch model card readers were evaluated by UL for compatibility with above-
mentioned Bosch Access Host Management System:
Bosch Security Systems B.V.
The maximum number of AMC2 controllers varies depending on the type of license
(AMC2-2WCF, downloader version 00.49 or higher, program version 37.xx).
Every controller can be extended with one AMC2-4WE.
Every controller can be extended with up to three AMC2-8IOE, AMC2-16IOE or AMC2-16IE
in any combination.
The enclosures AMC2-UL01 (for one device) or AMC2-UL02 (for two devices).
For every enclosure, a power supply Bosch APS-PSU-60 is necessary, and must be located
in the same room as the connected AMC2 device. Recommended maximum distance
between power supply unit and AMC2 is 3 m (9.84 ft).
LECTUS secure 1000 WI
LECTUS secure 4000 WI
LECTUS secure 5000 WI
LECTUS secure 9000 WI