Ul Requirements - Bosch AMC2 Series Installation Manual

Modular controller
Hide thumbs Also See for AMC2 Series:
Table of Contents

Advertisement

AMC2 Modular
Controller
5

UL Requirements

Before installing the AMC2-4W in the US market note and follow
the UL requirements described below.
Depending on the Host Management, the system consists of:
The Access Professional Edition (APE) 3.4 or 3.5 or Building
Integration System (BIS)- Access Engine (ACE) 4.5 as the Host
Management System. This is an Access Control (UL 294 ALVY)
system. It consists of the following devices - all listed to UL 294:
Notice!
The use of the burglar alarm, panic hardware, and elevator
control were not evaluated by UL.
For UL compliance, use only UL Listed 26-bit Wiegand format
readers.
The following Bosch model card readers were evaluated by UL
for compatibility with the Bosch's APE 3.4 and 3.5 or BIS/ACE
4.5 Software System:
Bosch Access Systems GmbH
Depending on the kind of license, a maximum number of
128 AMC2-4W controllers (downloader version 00.49 or
higher, program version 37.xx).
Every controller can be extended with one AMC2-4WE.
Every controller can be extended with up to three
AMC2-16IOE or AMC2-8IOE in any combination.
The enclosures AMC2-UL01 (for one device) or AMC2-UL02
(for two devices).
For every enclosure, a power supply Bosch APS-PSU-60 is
necessary, and must be located in the same room as the
connected AMC2 device. Recommended maximum distance
between power supply unit and AMC2 is 3 m (9.84 ft).
LECTUS secure 1000 WI
LECTUS secure 4000 WI
LECTUS secure 5000 WI
LECTUS secure 9000 WI
UL Requirements | en
2018-09 | AMC2-4W_UL |