40
en | Troubleshooting
7.2
Resetting the device to factory default
1.
2.
3.
4.
5.
6.
Figure 7.2: DIP switches
The controller now has the following network configuration:
–
–
–
–
2022-11 | V05 |
If connected to the Ethernet, release the connection.
Open the upper case of the controller as described in Opening the Case.
Reset the controller as described in Resetting the software, page 39 .
Set all six DIP switches of the RS-485 selector to ON (see figure below).
Press the reset button.
After completing this procedure, do not forget to set the DIP switches to your preferred
position (factory default 1 and 5 to ON).
DHCP = 1
IP = [assigned by DHCP server or "0.0.0.0" if not available]
Subnet mask = [assigned by DHCP server or "0.0.0.0" if not available]
Password = no password
–
Create your password in the IP Config settings of the AMC.