Calculating Power Requirements - Paradox Digiplex EVO48 V1.20 Installation Manual

High security and access system
Table of Contents

Advertisement

2.11

Calculating Power Requirements

Description
Grafica Graphic LCD Keypads (DNE-K07):
LCD Keypads (EVO641):
LCD Keypads with Built-in Reader (EVO641R):
LED Keypads (DGP2-648):
Motion Detector Modules (DG85, DGP2-50/60/70):
Door Contact Modules (DGP2-ZC1):
1-Zone Expansion Modules (DGP2-ZX1):
4-Zone Expansion Modules (APR3-ZX4):
8-Zone Expansion Modules (APR-ZX8):
Magellan Wireless Expansion Modules (MG-RTX3):
4-PGM Expansion Modules (APR3-PGM4):
Printer Modules (APR-PRT3):
DVACS Modules (DGP2-DVAC):
Annunciator Modules (DGP2-ANC1):
InTouch Voice-Assisted Arm/Disarm Modules (APR3-ADM2):
Hub and Bus Isolator (APR3-HUB2):
Access Control Module (DGP-ACM12):
Note: The DGP-ACM12 consumes 130mA from its own power supply.
The DGP-ACM11 consumes 120mA when connected on the combus for power.
Listen-In Module (DGP-LSN4)
Internet Module (IP100)
Plug-In Voice Module (VDMP3)
Other devices such as hardwired motion detectors
Maximum available milliamps = 700mA
1.
Using Table 1, calculate the total number of milliamps (mA) required by each device, module, and accessory in the system. Please take into account
devices connected to the control panel's PGM outputs. Since the
calculation.
2.
If Grand Total is less than 700mA, go to step 3. If the value is greater, an external power supply is required (see Figure 5 on page 5) to provide the
additional power needed. Proceed with step 3 and refer to the example in Figure 4 on page 5.
3.
Due to the degradation of a power signal over long distances, EACH length or run of wire in the system can support only a specific number of milliamps
(mA). Using Table 2, determine how many milliamps each length of wire can support. Please note that the total number of milliamps (mA) can never
surpass 700mA.
Gauge: 18AWG, Surface: 0.823mm
Length of each run
Available
of wire
milliamps (mA)
30m(100ft.)
700
61m(200ft.)
700
91m(300ft.)
700
122m(400ft.)
700
152m(500ft.)
690
183m(600ft.)
575
213m(700ft.)
493
244m(800ft.)
431
274m(900ft.)
383
305m(1000ft.)
345
457m(1500ft.)
230
610m(2000ft.)
172
762m(2500ft.)
138
914m(3000ft.)
115
4 Reference & Installation Manual
Table 1: Power Requirement Calculation
BELL
Table 2: Milliamps (mA) Limitations For Each Run of Wire
2
Gauge: 22AWG, Surface: 0.326mm
Length of each run
of wire
30m(100ft.)
61m(200ft.)
91m(300ft.)
122m(400ft.)
152m(500ft.)
183m(600ft.)
213m(700ft.)
244m(800ft.)
274m(900ft.)
305m(1000ft.)
QTY.
mA used by each
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
_______
X
GRAND TOTAL
output has its own power supply, do not include the sirens connected to it in the
2
Available
milliamps (mA)
700
682
454
341
273
227
195
170
151
136
Total mA
130mA =
__________ mA
110mA =
__________ mA
120mA =
__________ mA
110mA =
__________ mA
30mA =
__________ mA
15mA =
__________ mA
30mA =
__________ mA
30mA =
__________ mA
30mA =
__________ mA
35mA =
__________ mA
150mA =
__________ mA
25mA =
__________ mA
40mA =
__________ mA
20mA =
__________ mA
105mA =
__________ mA
50mA =
__________ mA
120mA =
__________ mA
60mA =
__________ mA
110mA =
__________ mA
35mA
=
__________ mA
__________ mA
__________ mA
Gauge: 24AWG, Surface: 0.205mm
Length of each run
Available
of wire
milliamps (mA)
30m(100ft.)
700
61m(200ft.)
429
91m(300ft.)
286
122m(400ft.)
214
152m(500ft.)
171
183m(600ft.)
143
2