Manufacturer's Information; Delivery; Packaging; Transport - GEM eSyDrive 567 Operating Instructions Manual

Aseptic control valve with motorized esydrive actuator
Table of Contents

Advertisement

9 Manufacturer's information

The controller required for valve operation is not included in
the scope of delivery.

9.1 Delivery

● Check that all parts are present and check for any damage
immediately upon receipt.
The product's performance is tested at the factory. The scope
of delivery is apparent from the dispatch documents and the
design from the order number.

9.2 Packaging

The product is packaged in a cardboard box which can be re-
cycled as paper.

9.3 Transport

1. Only transport the product by suitable means. Do not drop.
Handle carefully.
2. After the installation dispose of transport packaging ma-
terial according to relevant local or national disposal regu-
lations / environmental protection laws.

9.4 Storage

1. Store the product free from dust and moisture in its ori-
ginal packaging.
2. Avoid UV rays and direct sunlight.
3. Do not exceed the maximum storage temperature (see
chapter "Technical data").
4. Do not store solvents, chemicals, acids, fuels or similar
fluids in the same room as GEMÜ products and their spare
parts.

10 Installation in piping

10.1 Installation location

Do not apply external force to the valve.
Choose the installation location so that the valve cannot
be used as a foothold.
Lay the pipeline so that the valve body is protected
against transverse and bending forces, and also vibra-
tions and tension.
Only install the valve between matching aligned pipes.
Install the actuator horizontally for optimized draining.
The flow direction of the working medium is indicated by
an arrow on the valve body.
www.gemu-group.com
CAUTION
NOTICE
in closed and open position
Actuator horizontal
Control range
We recommend designing the valves in such a way that the
control range is within an opening stroke of 20% to 90% of the
control valve.

10.2 Preparing for installation

The equipment is subject to pressure!
▶ Risk of severe injury or death.
Depressurize the plant.
Completely drain the plant.
Corrosive chemicals!
▶ Risk of caustic burns.
Hot plant components!
▶ Risk of burns.
Exceeding the maximum permissible pressure.
▶ Damage to the product.
Provide precautionary measures against exceeding the
maximum permitted pressures caused by pressure
surges (water hammer).
Use as step.
▶ Damage to the product.
▶ Risk of slipping-off.
Choose the installation location so that the product can-
not be used as a foothold.
Do not use the product as a step or a foothold.
39 / 60
10 Installation in piping
in open position
Actuator horizontal or vertical
WARNING
WARNING
Wear suitable protective gear.
Completely drain the plant.
CAUTION
Only work on plant that has cooled
down.
CAUTION
CAUTION
GEMÜ 567 eSyDrive

Advertisement

Table of Contents
loading

Table of Contents