8.2.6 Memory for non-volatile application program variables

Properties
Types of access
JetSym STX
Program
Setup pane
User Manual – JetControl 365MC
Non-volatile variables are used to store data that must be maintained when the
JC-365MC is de-energized.
Global variables which are assigned to permanent registers (%RL)
Variables are stored in a compact manner, according to the size of their type
Size: 240,000 bytes (480,000 with -R option)
Register numbers: 1,000,000 ... 1,059,999 (up to 1,119,999 with option -R)
By JetSym
From HMIs
From within the application program
In the following program 4 non-volatile variables are incremented every second.
The working range of the counters is between 0 and 255 (variable type: byte). For
these 4 variables the 4 bytes of register 1000010 are used.
Var
    Cnt1, Cnt2, Cnt3, Cnt4: Byte
End_Var;
Task Count4Autorun
    Loop
        Inc(Cnt1);
        Inc(Cnt2, 2);
        Inc(Cnt3, 5);
        Inc(Cnt4, 10);
        Delay(T#1s);
    End_Loop;
End_Task;
The JetSym setup pane shows the content of the variable. Since the 4 counters
are of the byte type, this will result in counter overflow after a relatively short time.
Number Element
1
Current content of
the variable Cnt1
2
Current content of
the variable Cnt2
3
Current content of
the variable Cnt3
4
Current content of
the variable Cnt4
At
%RL 1000010;
Description
The content of the variable is incremented by 1
every second.
The content of the variable is incremented by 2
every second.
The content of the variable is incremented by 5
every second.
The content of the variable is incremented by
10 every second.
Programming | 8