Jetter AG
7.2.6 Setting the IP address
Replacing the
controller
Configuration
options
Changing the IP
address
User Manual – JetControl 365MC
Section in
Registers
config.ini
MR 64
PORTS
MR 65
MR 80
FILES
Tab. 40: Overview of configuration registers
To communicate via Ethernet, you must set a unique IP address on the con-
troller.
The IP address is stored in the configuration memory on the backplane module. If
you plug another controller of the same controller series onto the backplane mod-
ule, the following configuration data are retained:
■
IP address of the controller
■
Subnet mask
■
IP address of the default gateway
■
IP address of DNS server
■
Controller name
■
Suffix type of the name
■
IP port number for debugger
■
IP port number for JetIP
■
Name for AutoCopy command file
You can configure the IP address in the following ways:
■
Setting the default IP address
■
Configuration via file config.ini
■
Configuration via config.ini file and DIP switch
■
Configuration via the configuration registers (remanent)
■
Configuration during runtime via special registers (not remanent)
■
Configuration via JetIPScan program (remanent)
1.
Switch off the power supply to the device.
2.
Remove the controller enclosure from the backplane module.
3.
Make the corresponding DIP switch settings.
4.
Reattach the controller enclosure to the backplane module.
ð
After the restart, the device can be reached at the new IP address.
Name in config.ini Description
JetIPBase
IP port number for OS updates
and communication between
controllers
JVMDebug
IP port number for debugger/
setup in JetSym
AutoCopyIni
Name for AutoCopy command
file
Identification and Configuration | 7
59 / 148