Honeywell Experion 8 Series Technical Information page 14

Table of Contents

Advertisement

Series 8 Controller and I/O Specification, S803-150-500
Item
Specification
Electromagnetic compatibility (EMC) – Part 4-8: Testing and
measurement techniques – Power frequency magnetic field immunity
test
Electromagnetic compatibility (EMC) – Part 4-11: Testing and
measurement techniques – Voltage dips, short interruptions and
voltage variations immunity tests
Electrical Equipment for Use in Hazardous (Classified) Locations,
General Requirements
Non-incendive Electrical Equipment for Use in Class I and II, Division
2 and Class III, Division 1 and 2, Hazardous (Classified) Locations
Electrical and Electronic Test, Measuring and Process Control
1
FM
Equipment
Electrical apparatus for explosive gas atmospheres.
Part 0: General Requirements
Explosive atmospheres
Part 15: Equipment protected by type of protection "n"
Non-incendive Electrical Equipment for use in Hazardous Locations
Electrical and Electronic Test, Measuring and Process Control
Equipment
CSA
1
Electrical apparatus for explosive gas atmospheres.
Part 0: General Requirements
Explosive atmospheres
Part 15: Equipment protected by type of protection "n"
Non-incendive Electrical Equipment
for use in Hazardous Locations
Electrical and Electronic Test, Measuring and Process Control
Equipment
ATEX
1
Electrical apparatus for explosive gas atmospheres.
Part 0: General Requirements
Explosive atmospheres
Part 15: Equipment protected by type of protection "n"
Electrical apparatus for explosive gas atmospheres. Part 0: General
Requirements
IECEX
1
Explosive atmospheres
Part 15: Equipment protected by type of protection "n"
Note 1:
The installer shall provide transient over-voltage protection external to the apparatus such that the voltage at the supply terminal
of the apparatus does not exceed 140% of the voltage rating of the equipment.
The equipment shall be mounted in an enclosure providing a minimum degree of protection of IP54 in accordance with IEC
60079-15, and in a tool-secured enclosure which meets the requirements of IEC 60079-0 and IEC 60079-15.
The equipment shall be used in an area not more than Pollution Degree 2 as defined in IEC 60664-1.
Version 1
14
IEC61000-4-8
2009
IEC61000-4-11
2004
FM 3600
2011
FM 3611
2004
FM 3810
2005
ANSI/ISA-60079-0
2013
ANSI/ISA-60079-
2012
15
CAN/CSA C22.2
1987
No. 213 – M1987
(2013)
CAN/CSA-C22.2
2004
No. 61010-1-12
CAN/CSA
2011
E60079-0
CAN/CSA
2012
E60079-15
CAN C22.2
1987
No. 213 - M1987
(2013)
C22.2
2004
No. 1010.1
CAN/CSA
2011
E60079-0
CAN/CSA
2012
E60079-15
IEC 60079-0
2011
IEC60079-15
2010
July 2017